Design data PED (CE) approval |
||||||||
Version | Tubes side | Shell side | ||||||
DP (bar) | DT (°C) | Tmin (°C) | PT (bar) | DP (bar) | DT (°C) | Tmin (°C) | PT (bar) | |
STD | 10 | 90 | -10 | 14.3 | 30 | 120 | -10 | 42.9 |
HP | 16 | 90 | -10 | 22.9 | 48 | 120 | -10 | 68.6 |
DP Design Pressure | DT Design temperature | Tmin Minimum temperature | PT Test Pressure |
The XS-S-M in item’s description is set according to shell diameter and the chart below.
Dshell Min – Max range | ||||
mm | Inches | |||
XS | 51 | 168 | 2 | 6.63 |
S | 194 | 324 | 7.63 | 12.75 |
M | 356 | 457 | 14 | 18 |
L | 508 | 610 | 20 | 24 |
XL | 660 | 1007 | 26 | 42 |
Capacity Table
CRF serie has been optimized on three different shell sizes, according to the approach requested
CRF (Tower version – 2P) Ti = 30°C To = 35°C, SC = 3 [K], FF = 4.3E-05 [m²K/W] |
||||||||||||||||||||||
CRF Model 5 ft | 162-5 XS |
163-5 XS |
164-5 XS |
211-5 S |
212-5 S |
213-5 S |
214-5 S |
271-5 S |
272-5 S |
273-5 S |
274-5 S |
322-5 S |
323-5 S |
324-5 S |
401-5 M |
402-5 M |
403-5 M |
404-5 M |
452-5 M |
453-5 M |
454-5 M |
|
R407C Tc = 44.5°C (dew) Tg = 85°C |
Qn (kW) |
109 | 123 | 142 | 166 | 197 | 225 | 249 | 287 | 320 | 353 | 410 | 481 | 530 | 598 | 681 | 746 | 829 | 930 | 1003 | 1081 | 1151 |
R134a Tc = 40.0 Tg = 55°C |
Qn (kW) |
111 | 125 | 145 | 169 | 201 | 230 | 255 | 293 | 327 | 361 | 420 | 493 | 544 | 614 | 698 | 765 | 851 | 956 | 1030 | 1111 | 1184 |
CRF Model 6 ft | 162-6 XS |
163-6 XS |
164-6 XS |
211-6 S |
212-6 S |
213-6 S |
214-6 S |
271-6 S |
272-6 S |
273-6 S |
274-6 S |
322-6 S |
323-6 S |
324-6 S |
401-6 M |
402-6 M |
403-6 M |
404-6 M |
452-6 M |
453-6 M |
454-6 M |
|
R407C Tc = 43.0°C (dew) Tg = 85°C |
Qn (kW) |
111 | 125 | 145 | 168 | 200 | 229 | 253 | 292 | 325 | 359 | 417 | 489 | 540 | 608 | 692 | 758 | 843 | 946 | 1020 | 1100 | 1172 |
R134a Tc = 38.5 Tg = 55°C |
Qn (kW) |
106 | 119 | 139 | 161 | 192 | 220 | 244 | 280 | 312 | 345 | 401 | 471 | 520 | 586 | 667 | 731 | 814 | 914 | 985 | 1062 | 1132 |
CRF Model 7 ft | 162-7 XS |
163-7 XS |
164-7 XS |
211-7 S |
212-7 S |
213-7 S |
214-7 S |
271-7 S |
272-7 S |
273-7 S |
274-7 S |
322-7 S |
323-7 S |
324-7 S |
401-7 M |
402-7 M |
403-7 M |
404-7 M |
452-7 M |
453-7 M |
454-7 M |
|
R407C Tc = 42.0°C (dew) Tg = 85°C |
Qn (kW) |
113 | 126 | 147 | 170 | 203 | 233 | 257 | 296 | 330 | 365 | 424 | 497 | 548 | 618 | 704 | 770 | 858 | 962 | 1037 | 1117 | 1190 |
R134a Tc = 37.5 Tg = 55°C |
Qn (kW) |
101 | 114 | 132 | 153 | 183 | 210 | 232 | 266 | 298 | 329 | 382 | 448 | 495 | 558 | 636 | 697 | 775 | 870 | 938 | 1011 | 1079 |
Wm | (m³/h) | 22.4 | 26.5 | 30.6 | 34.7 | 42.9 | 48.9 | 54.0 | 61.3 | 69.3 | 76.5 | 88.7 | 103.9 | 116.1 | 132.7 | 150.8 | 165.3 | 183.6 | 207.6 | 224.4 | 241.8 | 262.6 |
Ti Inlet water temperature | To Outlet water temperature | SC Subcooling | FF Fouling factor | Tc Condensing temperature | Tg Inlet gas temperature | Qn Condensation capacity |
Wm Water maximum flow |
Evaporators
Application | Technology | Benefits |
The new CRF condenser has been developed for HFC cooling applications at medium pressure (PS 30 bar) and high pressure (PS 48 bar) within refrigeration, process cooling and air conditioning. The secondary fluid is usually fresh water that can be in a closed loop with a cooling tower (tower application) or in an open loop with a well (city application). Some applications can use also glycol. These applications usually require a condensation temperature in a range of +30°C/+50°C depending on the system working condition and its efficiency rating. |
The CRF design has been optimized for R407C/F and R134a refrigerants but it can be also utilized with HFO1234ze, R410A, R404A and R507. Thank's to its new high performance tubes, new headers, new shell and the new baffles, the Alfa Laval CRF models provide maximum efficiency with a low cost/kW. This is an important step ahead compared with the current CDEW and CDEW-E models; the new CRF is ready to fight with competition. |
|
Condensors